Quick Installation Guide
00825-0100-4697, Rev DB
September 2011
Rosemount 848T
12
Suitable for use in Class I, Division 2, Groups A, B, C, D. when installed per Rosemount
drawing 00848-4405.
Temperature Code:
T3C = (– 50 T
amb
60 °C)
Must be installed in a suitable enclosure as determined acceptable by the local
inspection authority.
I6 Intrinsically Safe, Division 2
For use in Class I, Division 1, Groups A, B, C, D; when installed per Rosemount drawing
00848-4405.
Temperature Code:
T3C (T
amb
= –50 to 60 °C)
Suitable for Class I, Division 2, Groups A, B, C, D. Rated 42.4 VDC max. Not valid with
S002 option.
IF FISCO (Intrinsically Safe)
For use in Class I, Division 1, Groups A, B, C, D; when installed per Rosemount drawing
00848-4405.
Temperature Code:
T3C (T
amb
= –50 to 60 °C)
Suitable for Class I, Division 2, Groups A, B, C, D.Rated 42.4 VDC max. Not valid with
S002 option.
N6 Class I, Division 2
Suitable for use in Class I, Division 2, Groups A, B, C, D. when installed per Rosemount
drawing 00848-4405.
Temperature Code:
T3C = (–50 T
a
60 °C)
Must be installed in a suitable enclosure as determined acceptable by the local
inspection authority.
Table 8. CSA Approved Entity Parameters
Power/Bus Sensor
(1)
(1) Entity parameters apply to entire device, not individual sensor channels.
V
max
= 30 V V
OC
= 12.5 V
I
max
= 300 mA I
SC
= 4.8 mA
C
i
= 2.1nF P
o
= 15 mW
L
i
= 0 C
A
= 1.2 F
L
A
= 1 H
Table 9. CSA Approved Entity Parameters
Power/Bus Sensor
(1)
(1) Entity parameters apply to entire device, not individual sensor channels.
U
i
= 17.5 V V
OC
= 12.5 V
I
i
= 380 mA I
SC
= 4.8 mA
P
i
= 5.32 W P
o
= 15 mW
C
i
= 2.1nF C
a
= 1.2 F
L
i
= 0 L
a
= 1 H