Section 4: Operation and Maintenance
November 2014
Operation and Maintenance
4.4.2 Resource block
4.4.3 Transducer block troubleshooting
Symptom Possible causes Corrective action
Mode will not leave
OOS
Target mode not set Set target mode to something other than OOS.
Memory Failure
BLOCK_ERR will show the lost NV Data or Lost Static Data bit set.
Restart the device by setting RESTART to Processor. If the block
error does not clear, call the factory.
Block Alarms Will not
work
Features FEATURES_SEL does not have Alerts enabled. Enable the report bit.
Notification LIM_NOTIFY is not high enough. Set equal to MAX_NOTIFY.
Symptom Possible causes Corrective action
Mode will not leave
OOS
Target mode not set Set target mode to something other than OOS.
A/D board check sum error The A/D board has a checksum error.
Resource block The actual mode of the Resource block is in OOS. See Resource
Block Diagnostics for corrective action.
Transducer Block The actual mode of the Transducer Block is OOS.
The primary value is
BAD
Measurement Look at the SENSOR_STATUS parameter (See Table 3-16 on
page 3-47
)