Reference Manual
00809-0100-4697, Rev GA
Appendix B: Product Certifications
November 2014
Product Certificates
IA ATEX FISCO Intrinsic Safety
Certificate: Baseefa09ATEX0093X
Standards: EN 60079-0:2012, EN60079-11:2012
Marking II 1 G Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +60 °C) when installed per drawing
00848-4406
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a degree of
protection of at least IP20. Non-metallic enclosures must be suitable to prevent
electrostatic hazards and light allow or zirconium enclosures must be protected
from impact and friction when installed.
2. The equipment is note capable of withstanding the 500V insulation test required
by EN 60079-11:2012, clause 6.3.13. This must be taken into account when
installing the equipment.
N1 ATEX Type n (with enclosure)
Certificate: Baseefa09ATEX0095X
Standards: EN 60079-0:2006, EN60079-15:2005
Marking II 3 G Ex nA nL IIC T5 (– 40 °C ≤ T
a
≤ + 65 °C)
Special Conditions for Safe Use (X):
1. Provision must be made, external to the apparatus, to ensure the rated voltage of
the apparatus supply is not exceeded by transient disturbances of more than 40.
2. The electrical circuit is connected directly to earth; this must be taken into
account when installing the apparatus.
NC ATEX Type n (without enclosure)
Certificate: Baseefa09ATEX0094U
Standards: EN 60079-0:2006, EN60079-15:2005
Marking II 3 G Ex nA nL IIC T4 (-50 °C ≤ Ta ≤ +85 °C), T5(-50 °C ≤ Ta ≤ +70 °C)
Table B-2. ATEX Entity Parameters
Fieldbus (Input)
Sensor Field Terminal
(Output)
U
i
= 30 V U
o
= 12.5 V
I
i
= 300 mA I
o
= 4.8 mA
P
i
= 1.3 W P
o
= 15 mW
C
i
= 2.1 nF C
o
= 1.2 μF
L
i
= 0 L
o
= 1 H
Table B-3. ATEX FISCO Entity Parameters
Power/bus Sensor
U
i
= 17.5 V U
o
= 12.5 V
I
i
= 380 mA I
o
= 4.8 mA
P
i
= 5.32 W P
o
= 15 mW
C
i
= 2.1 nF C
o
= 1.2 mF
L
i
= 0 L
o
= 1 H